您好,欢迎来到步遥情感网。
搜索
您的当前位置:首页《建筑电气施工手册》

《建筑电气施工手册》

来源:步遥情感网


第六章 建筑电气工程

目 录

1.配电箱(盘)安装···························································································1

2.电线、电缆导管和线槽敷设················································································9

3.电线、电缆导管和线槽敷线··············································································14

4.普通灯具安装·······························································································19

5.插座、开关、风扇安装····················································································22

6.建筑照明通电运行·························································································25

7.接地装置安装······························································································25

8.避雷引下线和变配电室接地下线敷设··································································31

9.建筑等电位连接····························································································33

北京惟明力通工程监理有限责任公司 建筑电气部分

1.配电箱(盘)安装

1.1 施工前期准备

序号 检查方式 控制项目 控 制 要 点 1) 安装配电箱(盘)孔洞预留尺寸是否合适、位置是否符合图纸要求; 备 注 1 巡视 检查施工2) 检查接地引线是否到位; 现场条件 3) 检查土建粉刷是否完毕,具备安装条件; 4)检查施工人员、工机具是否到位; 5)检查辅材是否合格 检查箱1) 再次核查箱(盘)防止二次搬运造成损坏; 3) 检查专用工具和易损件备品、门柜钥匙是否齐全,并妥 2 见证 (盘)到2) 检查箱(盘)内元器件是否完好,有无锈蚀; 场情况

- 1 -

北京惟明力通工程监理有限责任公司 建筑电气部分 善保管; 3

见证 检查技术准备条件 1) 检查有、无技术交底; 2) 检查施工人员上岗资格证书; 3) 检查施工单位质量保证体系能否正常开展工作; 1.2配电箱(盘)安装质量控制

序号 检查方式 控制项目 控 制 要 点 1) 基础型钢安装的不直度小于5mm/全长、水平度5mm/全 备 注 1 见证 基础型钢安装 长、位置误差及不平行度5mm/全长; 2) 基础型钢按装后,其顶部宜高出抹平地面10mm,并有明显可靠接地;

- 2 -

北京惟明力通工程监理有限责任公司 建筑电气部分 1) 箱(盘)安装在震动场所,应按设计要求采取防震措施; 2) 箱(盘)及内部设备与各构件间连接应牢固: 2 见证 箱(盘)3) 箱(盘)不宜与基础型钢焊死; 稳固 4) 箱(盘)应安装牢固,其垂直偏差不应大于3mm; 5) 箱(盘)暗装时,箱(盘)四周应无空隙,器面板四周边缘应进贴墙面,箱体与建筑物、构筑物接触部分应涂防腐漆;

1.3箱(盘)上电器安装 序检查方式 控制项目 号 1 见证 电器安装

控 制 要 点 1) 电气元件良好,型号、规格应符合设计要求,外观应完好, 且附件齐全,排列整齐,固 定牢固,密封良好; 备 注 - 3 -

北京惟明力通工程监理有限责任公司 建筑电气部分 2) 各电器应能单独拆装更换而不影响其它电器及导线束的固定; 3) 熔断器的熔体规格、自动开关的整定值应符合设计要求; 4) 信号回路的信号灯、光字牌、电铃、电笛、事故电钟等应显示准确可靠工作; 5) 盘上装有装置行设备或其它有接地要求的电器,器外科应可靠接地; 1) 端子应有序号,端子排应便于更换接线方便;离地高度宜大 于350mm; 2) 强、弱电端子宜分开布置;当有困难时,应有明显标志并设 2 见证 端子排安装 空端子隔开或设加强绝缘的隔板; 3) 潮湿环境宜采用防潮端子; 4) 二次回路的连接件均应使用铜质制品;绝缘件应采用自熄性阻燃材料; 5) 箱(盘)的正面及背面各电器、端子排等应标明线编号、名

- 4 -

北京惟明力通工程监理有限责任公司 建筑电气部分 称、用途及操作位置,其标明的自己应清晰、公正,且不易脱色 1.4箱(盘)二次回路接线质量控制 序号 检查方控制项式 目 固可靠。 箱(盘)1 见证 内二次回路接线 2) 盘、柜内的导线不应有接头,导线芯应无损伤; 3) 电缆芯线和所配导线的端部均应标明其回路编号,编号应正确,自己清晰且不易脱色; 4) 配线应整齐、清晰、美观,导线绝缘应良好,无损伤; 5) 每个接线端子的每侧接线宜为1根,不得超过2根。对于接插式端子,不同截面的两根 导线不得接在同一端子上;对于螺栓连接端子,当接两根导线时,中间赢家平垫片;

控 制 要 点 1) 导线与电气元件见采用螺栓连接、插件、焊接或压接等,均应牢备 注 - 5 -

北京惟明力通工程监理有限责任公司 建筑电气部分 6) 二次回路应设专用螺栓; 7) 盘、柜内的配线电流回路应采用电压不低于500V的铜芯绝缘导线,器界面不应小于2.5mm2;其它回路界面不应小于1.5mm2;对于电子元件回路、弱电回路采用锡焊连接时;在满足载流量和电压降基有足够机械强度的情况下,可采用不小于0.5mm2截面的绝缘导线; 8) 用于连接门上的电器控制台板等可动部位的导线尚应符合下列要求: 1应采用多股软导线,敷设长度应有适当裕度; ○2线束应有外套塑料管等加强绝缘层; ○3与电气连接时,端部应绞紧,并应加终端附件或搪锡,不得松○散、断股; 4在可动部位链段应用卡子固定。 ○2 见证 引入盘1) 引入盘、柜的电缆应排列整齐,编号清晰,避免交叉,并应固定内的缆

牢固,不得是所接端子排受机械应力; - 6 -

北京惟明力通工程监理有限责任公司 建筑电气部分 线连接 2) 铠装电缆在进入盘、柜后,应将钢带切断,切断处的端部应扎紧,并应将钢带接地; 3) 使用与静态保护、控制等逻辑回路的控制电缆,应采用屏蔽电缆。其屏蔽层应按设计要求的接地方式予接地; 4) 橡胶绝缘的芯线应外套绝缘管保护; 5) 盘、柜内的电缆芯线,应按垂直或水平有规律地配置,不得任意歪斜交叉连接。备用芯长度应留有适当余量; 6) 强、弱电回路不应使用同一根电缆,并应分别成束分开排列; 1.5工程试验 序检查号 方式 1 见证 控制项目 低压电器试验

控 制 要 点 1) 测量低压电器连同所连接电缆及二次回路的绝缘电阻; 2) 电压线圈动作值校验; 3) 低压电气动作情况检查; 备 注 - 7 -

北京惟明力通工程监理有限责任公司 建筑电气部分 4) 低压电气采用的脱扣器的整定; 5) 测量电阻器和变阻器的直流电阻; 6) 低压电器连同所连接电缆及二次回路的交流耐压试验; 7) 测量低压电气连同所连接电缆及二次回路的绝缘电阻值不应小于1MΩ:在比较潮湿的地方,可不小于0.5MΩ; 8) 低压电器动作情况的检查,应符合下述规定:对采用电动机或液压、气压传动方式操作的电气,处产品另有规定外每当电压、液压或气压在额定值的85%~110%范围内,电气应可靠工作; 9) 低压电器采用的脱扣器的整定,各类过电流脱扣器、失压和分励脱扣器、延时装置等,应按使用要求进行整定; 10) 低压电气连同所连接电缆及二次回路的交流耐压试验,应符合下述规定:试验电压为100V。当回路的绝缘电阻值在10MΩ以上时,可采用2500V兆欧表代替,试验持续时间为1min; 11) 漏电开关动作灵活可靠,动作电流不大于30mA,动作时间不大于0.1S。

- 8 -

北京惟明力通工程监理有限责任公司 建筑电气部分

1.6箱(盘)交接验收

序号 检查方式 控制项目 控 制 要 点 1) 检查配电箱(盘)的安装和回路编号; 备 注 配电箱1 见证 (盘)交接验收 2) 检查产品的说明说、合格证等技术文件、专用工具和备品备件; 3) 检查安装技术记录和试验记录;(包括影像资料) 4) 检查箱(盘)多余孔洞封堵、内部清理、控制回路标识、暗式箱盖固定、焊接防腐处理; 5) 做好进入维护期的各项和准备工作;

- 9 -

北京惟明力通工程监理有限责任公司 建筑电气部分

1.7配电箱(盘)安装安全管理 序号 作业项目 危险点 防范类型 倾倒、磕搬运 碰、砸伤 预 控 措 施 搬运时要齐心协力、互相照应提醒避开障碍物防止磕绊; 保持搬运通道通畅; 搬运时要绑牢、捆稳、垫好软垫,防止损伤人身、设备; 装卸时严禁野蛮抛、扔,轻装、轻卸; 使用砂轮切割机加工支架时,要防止砂轮片破裂伤人; 使用射钉稳固时,防止弹头回弹伤人; 配电箱2 (盘)支架制作、安装 使用电焊机时,检查好接地线和焊把线防止漏电伤人; 工具使人身伤按规定穿好防护服装,特别注意在潮湿环境下电焊作业的漏电按规定距离设置电焊机专用闸箱,保证一机、一闸、一漏、一箱、一锁; 进行电气焊作业时必须开具动火票,并按规定处理作业附近易

- 10 -

1 配电箱(盘)搬运 用不当 害、触电 保护;

北京惟明力通工程监理有限责任公司 建筑电气部分 燃物; 工作完毕撤离现场时,要注意关闭临时电源; 3 配电箱(盘)稳固 配电箱(盘)试验 就位安装 电气试验 倾倒、砸伤 触电 箱(盘)就位时,严禁野蛮搬撬,防止倾倒、坠落伤人和设备; 非试验人员不得随意操作试验设备; 试验过程中非试验人员严禁靠近试验设备; 正确使用试验设备,试验后要进行放电; 4 2.电线、电缆导管和线槽敷设

2.1电线导管敷设质量控制 序检查方式 号 1 见证 控制项目 控 制 要 点 备 注 线材、管1)材料外观良好,符合设计要求,三证齐全有效; 材进场

2)内外经符合相关规范规定,管壁厚度应均匀一致,无凸棱- 11 -

北京惟明力通工程监理有限责任公司 建筑电气部分 检查 凹陷,内外壁应光滑无毛刺; 3)螺栓、螺丝、膨胀螺栓、螺母、垫圈等应采用镀锌件; 4)金属灯头盒、开关盒、接线盒等,盒板厚度应符合华北标办图集的要求,镀锌层无脱落,无变形开焊,敲落孔完整无缺,面板安装孔与地线焊接脚齐全; 5)材料分批次进场,要按规定比例分批抽检,与样品核对; 6)检查材料保管条件,防止潮绣、变形和丢失等; 7)检查施工方材料采购计划落实情况; 8)代用材料必须取得甲方和设计同意,方能进场; 1) 路径、位置、方式符合设计规定; 2) 弯曲部分(弯曲半径、弯扁度)符合GB50303-2002规定; 3) 管口平整、光滑,管路横平、竖直; 4) 与其他管线的距离符合GB50303-2002规定; 5) 管线及附件防腐、接地或接零符合设计规定; 2 见证 管路配置

- 12 -

北京惟明力通工程监理有限责任公司 建筑电气部分 6) 在埋有电线保护管的大型设备基础模板上,应标有测量电线保护管引出口坐标和高程用的基准点或基准线; 7) 埋入建筑物、构筑物内的电线保护管、支架、螺栓等预埋件,应在建筑工程施工时预埋; 8) 预留孔、预埋件的位置和尺寸应符合设计要求,预埋件应埋设牢固; 9) 电气线路经过建筑物、构筑物的沉降缝或伸缩缝处,应装设两端固定的补偿装置,导线应有余量; 10)配线工程采用的管卡、支架、吊钩拉环和盒(箱)等黑色金属附件,均应镀锌或土防腐漆; 11)线路若有变化时必须及时在原图上进行标注,做竣工图时的依据,并及时办理变更或洽商,涉及费用时及时办理工程变更费用报审表;

- 13 -

北京惟明力通工程监理有限责任公司 建筑电气部分

2.2电缆导管敷设质量控制 序检查方式 号 控制项目 控 制 要 点 1) 材料外观良好,符合设计要求,三证齐全有效; 2) 内外经符合相关规范规定,管壁厚度应均匀一致,无凸棱凹陷,内外壁应光滑无毛刺; 1 见证 电缆管进3) 螺栓、螺丝、膨胀螺栓、螺母、垫圈等应采用镀锌件; 场检查 4) 材料分批次进场,要按规定比例分批抽检,与样品核对; 5) 检查材料保管条件,防止潮绣、变形和丢失等; 6) 检查施工方材料采购计划落实情况; 7) 代用材料必须取得甲方和设计同意,方能进场; 1) 每根电缆管的弯头数:一般弯头≤3个;直角弯头≤2个; 2 见证 电缆管制2) 弯曲部分(弯曲半径、弯扁度)符合GB50303-2002规作检查 定; 3) 电缆管内径按设计规定不小于1.5倍电缆外径,管内光滑

- 14 -

备 注

北京惟明力通工程监理有限责任公司 建筑电气部分 通畅,无积水、杂物; 1) 路径、位置、方式符合设计规定; 3 见证 电缆管敷设 2) 排灌敷设管口高度、弯曲弧度要一致; 3) 与其他管线的距离符合GB50168-1992表5.4.3规定; 4) 直埋管局地面深度(混凝土内除外)≥0.7m,伸出建筑物散水坡的长度≥2.5m、道路路基长度≥2m; 1) 金属管套管连接长度1.5D~3D电缆外径,管端套丝长度mm≥1/2接头长度; 2) 硬质塑料管套管两侧封焊牢固,密封良好;插接面有胶合4 见证 电缆管连接及其他 剂粘和牢固,密封良好;插入深度为1.1D~1.8D电缆外径; 3) 硬质塑料管补偿装置安装按GB50168-1992规定; 4) 金属软固定连接要牢固、紧固; 5) 电缆管接地应牢固,导通良好;

- 15 -

北京惟明力通工程监理有限责任公司 建筑电气部分

2.3线槽敷设质量控制

序号 检查方式 控制项目 控 制 要 点 1) 材料外观良好,符合设计要求,三证齐全有效; 2) 螺栓、螺丝、膨胀螺栓、螺母、垫圈等应采用镀锌件; 3) 材料分批次进场,要按规定比例分批抽检,与样品核对; 4) 检查材料保管条件,防止潮绣、变形和丢失等; 5) 检查施工方材料采购计划落实情况; 6) 代用材料必须取得甲方和设计同意,方能进场; 7) 线槽内外应光滑、平整、无棱刺,无扭曲、翘边等现象; 1) 检查弹线定位、预留孔洞是否符合设计要求; 2) 检查金属膨胀螺栓和预埋铁是否牢固,必要时做拉拔试验; 3) 检查支架与吊架安装是否牢固,位置是否准确、平直是否符合设计要求; 备 注 1 见证 线槽进场检查 2 见证 线槽安装检查

- 16 -

北京惟明力通工程监理有限责任公司 建筑电气部分 4) 检查线槽连接是否接口平整,交叉、转弯、丁字连接是否进行变通连接,接头处是否设置在接线和或电气器具内; 5) 检查线槽与盒、箱、柜等连接,进线和出线口等处是否应采用抱脚或翻边连接,并用螺丝紧固,末端是否加装封堵; 6) 检查线槽过墙或楼板孔洞时,四周是否留有50~100mm缝隙,接防火分区是否用防火材料封堵; 7) 检查敷设在竖井、吊顶、通道、夹层及设备层等处的线槽是否符合现行《建筑设计防火规范》; 8) 线槽内保护地线安装应按设计图要求敷设在线槽内一侧,接地处螺丝直径不应小于6mm,并且需要加平垫和弹簧垫去圈,用螺母压接牢固;

- 17 -

北京惟明力通工程监理有限责任公司 建筑电气部分

2.2电线、电缆导管和线槽安全管理 序号 作业项目 危险点 防范类型 预 控 措 施 机械设备的临时电源要按规定配置,确保漏电保护动作灵机械伤1 管、槽制作 机械加工 人、触电、划伤、灼伤 活、安全可靠; 做到一机、一闸、一箱、一漏、一锁; 加工场所必须按照规定设置灭火器具等安全消防设施; 现场不允许堆放易燃品; 及时清理废料,保持现场整洁; 合理配置机械位置,防止交叉作业误伤他人; 高处坠2 管、槽安装 高空作业 伤害 高处作业时,用梯子时,踢脚应有防滑橡皮垫,使用人自梯施工现场严禁嬉戏、打闹,防止意外事故发生; 检查施工单位安全保障运作情况; 检查安全措施落实情况,抽查安全记录;

- 18 -

落、人身时,中间要有保险拉链;

北京惟明力通工程监理有限责任公司 建筑电气部分

3.电线、电缆导管和线槽敷线

3.1施工前期准备

序号 检查方式 控制项目 控 制 要 点 1) 检查现场开始作业条件,管内穿线应在土建结构及施工墙 备 注 1 巡视 现场条件检查 面、地面抹灰动作完成后; 2) 线槽配线要求预留孔洞、预埋铁、预埋掉件、钓竿、吊架等全部完成,竖井内和前面的喷浆、油漆等完成后方可进行配线; 1) 导线的规格、型号必须符合设计要求,应有合格证、“CCC” 2 见证 进场材料检查

认证标志和认证证书复印件; 2) 镀锌铁丝或钢丝,应顺直无背扣、牛街,具有相应的机械拉力;; - 19 -

北京惟明力通工程监理有限责任公司 建筑电气部分 3) 护口:应根据管井大小选择相应的规格; 4) 安全行压线帽:可根据导线截面和根数选择和使用; 5) 套管:选用是应与导线、规格化相配套; 6) 接线端子:应根据导线的根数和总截面选择相应的规格; 检查施工1) 检查施工单位专项施工方案或技术交底; 3 见证 单位的技2) 检查施工单位人、机、料落实情况; 术准备情3) 核查图纸与现场预埋管路是否相符; 况 3.2工艺质量控制 序号 1 检查方式 控制项目 控 制 要 点 1) 配线所采用的导线型号、规格应符合设计规定; 巡视 导线型号 2) 当设计无规定时,不同敷设方式导线线芯的最小截面应符合和下列规定:

- 20 -

备 注

北京惟明力通工程监理有限责任公司 建筑电气部分 1穿管敷设的绝缘导线铜芯软线1.0mm2;铜线1.0mm2; ○铝线2.5mm2; 2槽板内敷设的绝缘导线铜线1.0mm2;铝线2.5mm2 ○导线与设备、器具的连接应符合下列要求: 1截面为10mm2及以下的单股铜芯线和单股铝芯线可之间与○设备、器具的端子连接; 2 巡视 导线连接 2截面为2.5mm2及以下的多股铜芯线的线芯应先拧紧搪锡○或压接端子后再与设备、器具的端子连接; 3多股铝芯线和截面大于2.5mm2的多股铜芯线的终端处设○备自带插接式端子外,应焊接或压接端子后再与设备、器具的端子连接; 剖开导线绝缘层时,不应损伤芯线;芯线连接后,绝缘带应3 巡视 剖线工艺 包缠均匀紧密,器绝缘强度不应低于导线原绝缘层的绝缘强度;在接线端子的根部与导线绝缘层的空隙处,应采用绝缘带包缠严密;

- 21 -

北京惟明力通工程监理有限责任公司 建筑电气部分 4 巡视 分支连接 在配线的分支连接处,干线不应受到直线的横向拉力 当配线选用多相导线时,其相线的颜色应易于区分,相线与零线的颜色应不同,统一建筑物、构筑物内的导线,其颜色选择应统一;保护地线(PE线)应采用黄绿颜色相间的绝缘导线;零线宜采用淡蓝色绝缘导线。 5 巡视 相序控制 3.3线槽敷线 序号 检查方式 控制项目 控 制 要 点 1) 导线的规格和数量应符合设计规定;当务设计规定时,包括绝缘层在内的大导线总结面积不应大于线槽面积的60% 1 巡视 线槽敷线 2) 在可拆卸高般的线槽内,包括绝缘层在内的导线接头处所有导线截面积之和,不应大于线槽截面积的75%;在不易拆卸盖板的线槽内,导线的接头应置于线槽的接线盒内; 3) 金属线槽应可靠接地或接零,但不应作为设备的接地导体。

- 22 -

备 注

北京惟明力通工程监理有限责任公司 建筑电气部分 4) 线槽内电缆敷设应符合以下规定: ①大于45°倾斜敷设的电缆每隔2m处设固定点; ②水平敷设的电缆首位两端、转弯两侧及每隔5~10m处设固定点; 5) 电缆处如电缆沟、竖井、建筑物、柜(盘)、台、管口处等做密封处理; 6) 电缆敷设排列整齐,首末端和分支处应设标志牌; 7) 导线间和导线对地间的绝缘电阻值必须大于0.5МΩ; 8) 同一回路的相线和零线敷设于同一线槽内; 9) 同一电源的不同回路无抗干扰要求的线路可敷设于同一线槽内;同一线槽内有抗干扰要求的线路用隔板隔离或采用屏蔽线,屏蔽层一段接地; 3.4管内配线 序检查方控制项目

控 制 要 点 - 23 -

北京惟明力通工程监理有限责任公司 建筑电气部分 号 式 1) 接线盒、开关盒、插销盒及灯头盒内导线的预留长度应为150mm; 2) 配电箱内导线的预留长度应为配电箱体周长的1/2; 3) 穿入管内的绝缘导线,不准接头、局部绝缘破损及死弯。导线外径总面截积不应超过管内面积的40%; 备注 1 巡视 管内配线 4) 导线规格、型号必须符合设计要求和国家标准的规定; 5) 三相或单相交流单芯电线、电缆,不得单独穿于钢管内; 6) 照明线路的绝缘电阻值不小于0.5МΩ,动力线路的绝缘电阻值不小于1МΩ; 7) 爆炸危险环境照明线路的电线、电缆额定电压不得低于750V,且必须穿插于钢管内。 3.5交接验收 序检查方控制项目

控 制 要 点 - 24 -

北京惟明力通工程监理有限责任公司 建筑电气部分 号 式 工程交接验收时,应对下列项目进行检查: 1) 各种规定的距离; 2) 明配线路的允许偏差值; 3) 导线的连接和绝缘电阻; 4) 非带电金属部分的接地或接零; 工程交接验收时,应提交技术资料和各种文件及试验记录等。 3.6电线、电缆导管和线槽敷线安全管理

备注 1 巡视 管内配线 序号 作业项目 电线、危险点 防范类型 高处坠落、代线扎伤 预 控 措 施 1) 高处作业时,用梯子时,踢脚应有防滑橡皮垫,使用人自梯时,中间要有保险拉链; 2) 拽拉引代线时,要一送一拉防止接头突然断裂,坠落伤人;引代线临出管口时,用力要适当; 1 电缆导高空作业、人管和线槽敷线

身伤害 - 25 -

北京惟明力通工程监理有限责任公司 建筑电气部分 3) 掐断引代线时,要捏紧掐断处钢丝,防止回弹伤人。 4普通灯具安装

4.1施工前期准备 序号 检查方式 控制项目 1) 安装灯具的预埋螺栓、吊杆和吊顶上用于嵌入式灯具安装的专用骨 1 巡视 现场条架等已完成,大型灯具的吊钩作完承载试验并合格; 3) 室内吊顶龙骨安装已经完成 1) 灯具的规格、型号、数量、安装方式、使用场所及相关资料是否符 2 见证 进场材料检查 合现场要求,灯具的配件齐全,外观完好,无变形,标志正确清晰;所有灯具应有合格证、生产许可证、“CCC”认证标识;安全疏散指示灯必须有消防部门备案证书; 2) 灯具导线应有产品合格证、生产许可证、“CCC”认证标识,倒显

- 26 -

控 制 要 点 备 注 件检查 2) 盒内清洁无杂物,固定件完好无损,盒口已修好;

北京惟明力通工程监理有限责任公司 建筑电气部分 得电压等级不应低于500V,且其最小线芯截面应符合室内:铜芯软线0.5mm2、铜线 1.0mm2;室外:铜芯软线1.0mm2、铜线 1.0mm2 3) 高空安装的灯具地面通电试验合格; 4) 导线绝缘测试合格; 检查施1) 检查施工单位专项施工方案或技术交底; 工单位2) 核查图纸与现场预埋件是否相符; 3 见证 的技术3) 与业主方共同对照图纸核查特殊部位现场额特殊要求是否能够得准备情况 4.2灯具安装 序号 1 检查方式 巡视 控制项目 装

到使用要求,必要时提请设计做设计作相应调整; 控 制 要 点 备 注 灯具安1) 吊链灯具的灯线不应受拉力,等闲英语吊链编叉在一起; 2) 软线吊灯的软线两端应作保护扣;两端芯线应搪锡; - 27 -

北京惟明力通工程监理有限责任公司 建筑电气部分 3) 同一室内或场所成排安装的灯具,其中新鲜偏差不应大于5mm; 4) 公共场所的应急照明灯和疏散指示灯,应有明显的标志。无专人管理的公共场所照明宜装设自动节能开关; 5) 每套路灯应在相线上装设熔断器。有架空线引入路灯的导线,在灯具入口处应作防水弯; 6) 当掉等等局重量大于3Kg时,应采用预埋吊钩或螺栓固定;当软线吊灯灯具重量大于1Kg时,应增设吊链; 7) 灯具安装高度宜大于5m,导线应经接线柱与灯具连接,且不得靠近灯具表面; 8) 灯具应固定在专设的框架上,导线不应贴近灯具外壳,且在灯盒内应留有余量,灯具的边框应紧贴在顶棚的面上; 9) 固定花灯的吊钩,其圆钢直径不应小于灯具吊挂销、钩的直径,且不得小于6mm。对大型花灯、吊装花灯的固定及悬吊装置,应按灯具重量的1.25倍做过载试验; 10) 安装在重要场所的刀型灯具的玻璃罩,应按设计要求采取防止

- 28 -

北京惟明力通工程监理有限责任公司 建筑电气部分 碎裂后向下溅落的措施。 11) 应急照明线路应在每个防火分区的应急照明回路,穿越不同防火分区的陷落由防火 隔堵措施; 12) 金属立柱及灯具可接近裸露导体姐弟(PE)或接零(PEN)可靠。接地线单设干线,干线沿庭院等布置位置形成环网状,且不少于2处于接地装置引出线连接。有干线引出支线与金属等主机灯具的接地端子连接,且有标识; 4.3灯具安装质量检查 序号 检查方式 控制项目 控 制 要 点 1) 检查因出现和灯具端子连接是否紧固,绝缘良好; 灯具安2) 检查中心线横向移位是否≤50mm; 1 巡视 装质量3) 检查垂直误差是否歪斜不明显; 检查

备 注 4) 检查接线处绝缘处理是否爆炸紧密、均匀,且不低于绝缘强度; 5) 检查金属外壳接地或接零是否符合GB 50169-1992 规定; - 29 -

北京惟明力通工程监理有限责任公司 建筑电气部分

5插座、开关、风扇安装

5.1插座安装 序号 检查方式 控制项目 要求: 1距离地面高度不宜小于1.3m;托儿所、幼儿园及小学及小学校 ○不宜小于1.8m;同一场所安装的插座高度应一致。 1 巡视 插座安装 2落地插座应具有牢固可靠的保护盖板。 ○2)单相两孔插座,面对插座的右孔或上孔与相线相接,左孔或下孔于零线相接;单相三孔插座,面对插座的右孔与相线相接,左空与零线相接。 3)单相三孔、三相四孔及三相五孔插座的接地线或接零线均应截在上孔。插座的接地端子不应与零线端子直接连接。 4)当交流、直流或不同电压等级的插座安装在同一场所时,应有明

- 30 -

控 制 要 点 备 注 1) 插座的安装高度应符合设计的规定,当设计无规定是,应符合下列

北京惟明力通工程监理有限责任公司 建筑电气部分 显区别,且必须选择不同结构、不同规格和不能互换的插座;其配套的插头,应按交流、直流或不同电压等级区别使用。 5)暗装的插座应采用专用盒;专用盒的四周不应有空隙,且盖板应端正,并紧贴墙面。 5.2开关安装 序号 检查方式 控制项目 控 制 要 点 备 注 1) 安装在同一建筑物、构筑物内的开关,应采用同一系列的产品,开 关的通断位置应一致,且操作灵活、接触可靠。 2) 并列安装的相同型号开关局地面高度应一致,高度不应大于1 巡视 开关安1mm;同一室内安装的开关高度差不应大于5mm;并列安装的拉线装 开关的相邻间距不宜小于20mm。 3) 相线应经开关控制;民用住宅严禁装设床头开关。 4) 暗装的开关应采用专用盒;专用盒的四周不应有空隙,且盖板应端正。

- 31 -

北京惟明力通工程监理有限责任公司 建筑电气部分

5.3风扇安装 检查方式 序号 控制项目 控 制 要 点 备 注 1) 风扇选吊挂销钉应装设防震橡胶垫;销钉的防松装置应齐全、可靠。 2) 风扇组装时应符合下列要求: 1 巡视 开关安装 1严禁改变扇叶的角度; ○2扇叶的固定应装设防松装置; ○3) 风扇接线应正确,运转时山也不应由明显的颤动。 4) 风扇的防护罩应扣紧,固定可靠,运转时扇叶和防护罩均不应有明显的颤动和异常声响。 6建筑照明通电运行

序号 1 检查方式 见证 控制项目 控 制 要 点 备 注 - 32 -

通电运1) 照明箱应有标识。 行检查 2) 照明箱应有接地。

北京惟明力通工程监理有限责任公司 建筑电气部分 3) 照明开关命名应与回路对应。 4) 应做漏电保护动作试验、应急灯试投实验、交、直流电源自动切换试验、光电控制器实验、直流长明灯投入、照明通电试验试运行

7接地装置安装

7.1施工前期准备 序号 检查方式 控制项目 控 制 要 点 备 注 1) 电气装置需要接地或接零及可不接地或不接零,以及需要接地的直 接地装1 见证 置的选择 流系统的接地装置的要求见GB 50169 -2006; 2) 接地装置的选择: 1可以利用的自然接地体如:埋设在地下的金属管道,但不包由可 ○燃或有爆炸物质的管道、金属景观、与大地有可靠连接的建筑物的金属结构、水工构筑物及其类似的构筑物的金属管、桩。

- 33 -

北京惟明力通工程监理有限责任公司 建筑电气部分 2交流电气设备的接地线可利用下列自然接地体接地:建筑物的 ○金属结构(梁、柱)及设计规定的混凝土结构内部的钢筋;生产用的起重机的轨道、走廊、平台、电梯竖井、其中给予升降级的构架、运输皮带的钢梁、电除尘器的构架等金属结构;配线的钢管 3) 人工接地网的外缘应闭合,外缘各角应做成圆弧形,圆弧的半径不宜小于均压带间距的一半;接地网内应敷设水平均压带,案等间距或不等间距布置。 4) 处临时接地装置外,接地装置应采用热镀锌钢材,水平敷设的可采用圆钢和扁钢,垂直辐射的可采用角钢和钢管。腐蚀比较严重地区的接地装置,应适当加大截面,或采用阴极保护等措施。不得采用铝导体作为接地体或接地线。当采用边钢带、铜绞线、铜棒、铜包钢、铜包钢绞线、刚都统、钱包同等材料作为接地装置时,器连接应符合本规范规定。不得利用蛇皮管、管道保温层的金属外壳或金属网、低压照明网络导线铅皮以及电缆金属护层做接地线。蛇皮管

- 34 -

北京惟明力通工程监理有限责任公司 建筑电气部分 两端均应采用自固接头或软管接头,且两端应采用软铜线连接。

7.2接地装置的敷设

序号 检查方式 控制项目 控 制 要 点 1) 接地体顶面埋设深度应符合设计规定。当无规定时,不应小于0.6m。角钢、钢管、铜棒、通关等接地体应垂直配置。除接地体外,接地体引出线的垂直部分盒接地装置连接(焊接)部位外侧100mm范围内应做防腐处理;在做防腐处理前,表面必须除锈并去掉焊接处残留的焊药。 2) 垂直接地体的间距不宜小于长度的2倍。水平接地体的间距应符合设计规定。当无设计规定时不宜小于5m。 3) 接地干线应在不同的两点及以上与接地网相连截。自然接地体应在备 注 接地装1 见证 置的敷设

- 35 -

北京惟明力通工程监理有限责任公司 建筑电气部分 不同的两点及以上与接地干线或接地网相连接。 4) 每个电气装置的接地应以单独的接地线与接地汇流排或接地干线相连接,严谨在一个接地险种串几个需要接地的电气装置。重要设备和设备构架应有两根与驻地网不同地点连接的接地引下线,且每根接地引下线均应符合热稳定及机械强度的要求,连接引线应便于定期进行检查测试。 5) 明敷接地线支持件间的距离,在水平直线部分宜为0.5~1.5mm,垂直部分宜为1.5~3m;转弯部分宜为0.3~0.5m; 6) 接地引线沿建筑物墙壁水平敷设,离地面距离宜为250~300mm;接地线与建筑物墙 壁间的间隙宜为10~15mm; 7) 明敷接地线,在导体的全长度或区间段及每个相连接部位附近的表面,均应涂以10~100mm宽度相等的绿色和黄色相间的条纹标识。当使用胶带时,应使用双色胶带。中性线宜涂淡蓝色标识。 8) 接地装置由多个分接地装置部分组成时,应按设计要求设置便于分开的断接卡,自然接地体与人工接地体连接处应有便于分开的断

- 36 -

北京惟明力通工程监理有限责任公司 建筑电气部分 接卡。断接卡应有保护措施。扩建接地网时,新、旧接地网连接应通过接地井多点连接。

7.3接地体(线)的连接 序号 检查方式 控制项目 控 制 要 点 1) 接地体(线)的连接应采用焊接,焊接必须牢固无虚焊。接至 电气设备上的接地线,应用镀锌螺栓连接;有色金属接地线不能采用焊接时,可用螺栓连接、压接、热焊剂(放热焊接)接地体1 见证 (线)的连接 方式连接。用螺栓连接时应设防松螺帽或防松垫片,螺栓连接处的接触面应按现行国家标准《电气装置安装工程 母线装置施工及验收规范GBJ 149的规定处理。不同材料接地体间的连接应进行处理。 2) 接地体(线)的焊接应采用搭接焊,其搭接长度必须符合扁钢为其宽度的2倍(至少三个棱边焊接);圆钢为其直径的6

备 注 - 37 -

北京惟明力通工程监理有限责任公司 建筑电气部分 倍;圆钢与扁钢连接时,其长度圆钢直径那个的6倍。扁钢与钢管、扁钢与角钢焊接时,为了连接可靠,除应在其接触部位两侧进行焊接外,并应焊以由钢带弯成的弧形(或直角形)卡子或直接由钢带本身弯成弧形(或直角形)与钢管(或角钢)焊接。 3) 采用钢绞线、铜绞线等做接地引下线时,宜用压接端子与接地 体连接。 4) 沿电缆桥架敷设铜绞线、镀锌扁钢及利用沿桥架构成电器通路的金属构件,如安装托架用的金属构件作为接地干线时,电缆桥架接地时应符合:电缆桥架全长不大于30m时,不应少于2处与接地干线相连;全场大于30m时,应每隔20~30m增加与接地干线的连接点;电缆桥架的起始端和终点端应与地网可靠连接。

- 38 -

北京惟明力通工程监理有限责任公司 建筑电气部分

7.4接地装置安装安全要点 作业项目 序号 危险点 防范类型 预 控 措 施 1) 埋设接地装置时,要防止大锤脱落伤人,沟壁坍塌。 1 接地装高空作业、人高处坠2) 安装接闪器时要戴好安全带防止坠落。 置安装 身伤害 落、 3) 安装引下线时,要有专人扶梯,防止倾倒、滑坠伤人。 4) 要按安全规程使用电焊机。

8避雷引下线和变配电室接地引下线敷

8.1避雷引下线的焊接

序号 检查方式 控制项目

控 制 要 点 备 注 - 39 -

北京惟明力通工程监理有限责任公司 建筑电气部分 1) 避雷针与引下线之间的连接应采用焊接。 2) 避雷针的引下线及接地装置之用的紧固件均应使用镀锌件。 3) 建筑物上的防雷设施采用多根引下线时,宜在各引下线距地面的1.5~1.8处设置断接卡,断接卡应加保护措施。 4) 装有避雷针的金属筒体,当其厚度不小于4mm时,可做避雷针的引下线。筒体底部应有两处与接地体对称连接。 避雷引5) 避雷针及其接地装置与道路或建筑物的出入口等的距离应大1 见证 下线焊接 于3m。当小于3m时,应采取均压措施或铺设卵石或沥青路面。 6) 避雷针应设置的集中接地装置。当有困难时,该接地装置可与接地网连接,但避雷针与主接地网的地下连接点至35KV及以下设备与主接地网的地下连接点,沿接地体的长度不得小于15m。 7) 避雷针的接地装置与接地网的地中距离不应小于3m。 8) 配电装置的构架或屋顶上的避雷针应与接地网连接,并应在其附近装设集中接地装置。

- 40 -

北京惟明力通工程监理有限责任公司 建筑电气部分 9) 建筑物上的避雷针或防雷金属网应和建筑物顶部的其他金属物体连接成一个整体。 10) 装有避雷针和避雷线的构架上的照明灯电源线,必须采用直埋于土壤中的带金属护层的电缆或传入金属管得导线。电缆的金属护层或金属管必须接地,埋入土壤中的长度应在10m以上,方可与配电装置的接地网相连或电源线、低压配电装置相连接。

8.2变配电室接地引下线敷设 序号 检查方式 控制项目 配电电1 见证 气装置的接地

控 制 要 点 备 注 1) 户外配电变压器等电气装置的接地装置,宜在地下敷设成围绕变压 器台的闭合环形。 2) 引入配电装置室的每条架空线路安装的避雷器的接地线,应与配电装置室的接地装置连接,但在入地处应敷设集中接地装置。 - 41 -

北京惟明力通工程监理有限责任公司 建筑电气部分 3) 配电电气装置的接地电阻值应符合设计要求。 4) 按照电气装置的要求,安全接地,保护接地或功能接地的接地装置可以采用共用的或分开的接地装置。

9建筑等电位连接

序号 检查方式 控制项目 控 制 要 点 备 注 1) 按照电气装置的要求,安全接地,保护接地或功能接地的接地装置 可以采用共用的或分开的接地装置。 建筑等1 见证 电位连接 2) 建筑物的低压系统接地点、电气装置外露导电部分的保护接地(含与功能接地、保护接地共用的安全接地)、总等电位联结的接地极等可与建筑物的雷电保护接地共用同一接地装置。接地装置的接地电阻应符合其中最小要求。 3) 电气装置应设置总接地端子或母线,并与接地线、保护线、等电位

- 42 -

北京惟明力通工程监理有限责任公司 建筑电气部分 连接干线和安全、功能共用接地装置的功能性接地线等相连接。 4) 等电位联结主母线的最小截面机不应小于装置最大保护线截面的一半,并不应小于6mm2。当采用铜线时,其截面不应小于2.5mm2。当采用其他金属时,则截面应承载与之相当的载流量。 5) 联结两个外露到点部分的辅助等电位联结线,其界面不小于接至改两个外露导电部分的叫嚣保护线的截面。连接外露导电部分与装置外导电部分的辅助等电位联结线,其截面不应小于相应保护线截面的一半。

- 43 -

因篇幅问题不能全部显示,请点此查看更多更全内容

Copyright © 2019- obuygou.com 版权所有 赣ICP备2024042798号-5

违法及侵权请联系:TEL:199 18 7713 E-MAIL:2724546146@qq.com

本站由北京市万商天勤律师事务所王兴未律师提供法律服务